Cable & Wire Size Calculator

Choosing an appropriate cable or wire size is an important part of electrical circuit design.

A conductor that is too small can produce excessive voltage drop and power loss. It can also overheat if its current-carrying capacity is insufficient for the installation conditions.

The Cable & Wire Size Calculator helps estimate conductor cross-sectional area and voltage drop for DC, single-phase and balanced three-phase circuits.

You can calculate a required conductor area from a maximum voltage-drop limit, check the voltage drop of an existing wire, and convert between American Wire Gauge (AWG) and square millimetres (mm²).

The results are based on the inputs and assumptions displayed by the calculator. Final cable selection must also satisfy the applicable wiring regulations and installation requirements.

Load Example:
%
°C
Conductor Cross-Section & Circuit RunCopper • 10 mm²
d = 3.568 mmArea: 10 mm²Current I →Load11.6552 VOne-Way Length: 5 m | ΔV = 344.8 mV

Voltage-drop estimate only. Ampacity has not been verified. Final cable selection requires applicable local standards.

Recommended Next Standard Size (Voltage-Drop Basis)Nearest ≈ 7 AWG (10.55 mm²)
10 mm²
Voltage Drop: 344.8 mV (2.873%) • Voltage at Load: 11.6552 V
Minimum Required Cross-Section
9.5778 mm²
Recommended Next Standard Size (Voltage-Drop Basis)
10 mm²
AWG Equivalent
Nearest ≈ 7 AWG (10.55 mm²)
Conductor Diameter
3.568 mm
Actual Voltage Drop
344.8 mV
(2.873%)
Voltage at Load
11.6552 V
Conductor Resistance (1-Way / Loop)
8.62 mΩ / 17.24 mΩ
Power Loss
6.896 W

Calculation Assumptions: Two-conductor outgoing + return loop (factor 2). Final cable selection requires verification against ampacity tables, installation method, ambient temperature, grouping, and local electrical standards.

  1. 1ρ(20°C) = 1.724 × 10⁻⁸ Ω·m (Annealed Copper)
  2. 2ΔV_max = 3% × 12 V = 360 mV
  3. 3A_min = 9.5778 mm² → Next standard size: 10 mm²
  4. 4Actual ΔV (10 mm²) = 344.8 mV (2.873%)
  5. 5Load Voltage = 11.6552 V, Power Loss = 6.896 W

What Is Cable Size?

Cable size commonly refers to the cross-sectional area of the conductor, normally expressed in square millimetres (mm²). AWG is another system used to describe wire size.

A larger conductor cross-sectional area generally has lower electrical resistance for the same material and length. However, cable size alone does not determine its current-carrying capacity. Insulation, installation method, conductor temperature, ambient conditions and grouping also matter.

How to Use the Calculator

  1. Select DC, single-phase or three-phase.
  2. Enter the supply voltage.
  3. Enter the load current.
  4. Enter the one-way cable length.
  5. Select the allowable voltage-drop percentage.
  6. Select copper or aluminium.
  7. Enter the conductor temperature.
  8. Select the output unit system.
  9. Calculate the minimum area based on voltage drop.
  10. Review the next suitable standard size and actual calculated voltage drop.

Understanding Voltage Drop

Voltage drop is the reduction in electrical voltage along a conductor when current flows through its resistance. Longer cables and higher currents generally produce greater voltage drop, while larger cross-sections reduce resistance. Check fundamental resistive relationships with the Ohm's Law Calculator and Voltage Divider Calculator.

DC / 2-Wire Drop: ΔV = 2ρLI / A

Single-Phase & Three-Phase Circuits

Single-phase two-wire circuits include outgoing and return conductors. Balanced three-phase circuits apply a √3 factor instead of 2. The simplified three-phase calculation uses a resistive approximation; conductor reactance can become important in longer or larger AC installations (analyse complex AC circuits in our Impedance Calculator).

Copper vs Aluminium

For equal length and cross-sectional area, aluminium (2.824 × 10⁻⁸ Ω·m at 20°C) has higher resistance than copper (1.724 × 10⁻⁸ Ω·m at 20°C), so a larger aluminium conductor is needed for the same voltage drop.

AWG and mm² Conversion

As AWG increases, wire diameter and area decrease. Always distinguish mathematical area equivalence, nearest standard metric size, and the next standard metric size that meets or exceeds a required area. For paralleled conductors check total resistance with the Parallel Resistor Calculator.

Temperature Correction

Resistivity scales linearly near operating temperatures via ρ_T = ρ₂₀ [1 + α(T − 20)]. This estimates conductor resistance shift with temperature and does not replace manufacturer resistance tables.

Worked Example — DC Wire Size

12 V DC, 20 A, 5 m one-way, 3% max drop, Copper at 20°C:

ΔV_max = 12 × 0.03 = 0.36 V

A = 2 × 0.01724 × 5 × 20 / 0.36 ≈ 9.5778 mm²

Next standard metric size: 10 mm²

Actual ΔV = 0.3448 V (2.873%)

Important: This verifies voltage drop only, not installation ampacity.

Worked Example — Three-Phase Voltage Drop

400 V three-phase, 100 A, 50 m one-way, 25 mm² Copper at 20°C:

ΔV = √3 × 0.01724 × 50 × 100 / 25 ≈ 5.972 V

%ΔV = 5.972 / 400 × 100 ≈ 1.493%

This is a simplified resistive estimate, not a full installation compliance calculation.

Cable Current-Carrying Capacity & Safety Limitations

Current-carrying capacity (ampacity) depends on conductor material, cross-section, insulation type, maximum conductor temperature, number of loaded conductors, installation method, ambient temperature, grouping, soil thermal resistivity (buried cables), and protective-device coordination (e.g. IEC 60364-5-52 and IEC 60287).

This calculator is an engineering estimation and educational tool. Unless a documented standard-specific current-rating engine is separately implemented, it does not certify current-carrying capacity, overcurrent protection, short-circuit withstand, earth-fault protection, fire safety, or code compliance. Always consult a qualified electrical professional and applicable local regulations.

Applications

Cable and wire calculations are useful for:

  • DC power distribution.
  • Battery connections.
  • Automotive wiring.
  • Solar installations.
  • Electrical equipment connections.
  • Single-phase circuits.
  • Three-phase feeders.
  • Electronic systems & AWG/mm² conversion.

Common Mistakes

  • Using total round-trip length where the formula already includes a factor of two.
  • Mixing metres and feet or AWG and mm².
  • Confusing conductor diameter with cross-sectional area.
  • Ignoring temperature and voltage drop.
  • Treating a voltage-drop result as an ampacity check.
  • Assuming the nearest metric size is always the next larger size.
  • Ignoring installation-specific correction factors.

Frequently Asked Questions

1. What is a cable size calculator?

It estimates conductor cross-sectional area from electrical load, cable length and selected voltage-drop requirements.

2. What is the difference between AWG and mm²?

AWG is a numbered gauge system, while mm² expresses the conductor's nominal cross-sectional area directly.

3. Does a larger wire reduce voltage drop?

Generally, yes. A larger cross-sectional area reduces conductor resistance for the same material and length.

4. Does copper have lower resistance than aluminium?

For equal conductor dimensions and comparable conditions, copper generally has lower electrical resistance.

5. Why does cable length affect voltage drop?

Longer conductors have greater total resistance, which produces greater voltage drop for a given current.

6. Can this calculator guarantee a safe cable size?

No. A voltage-drop result does not establish current-carrying capacity or code compliance.

7. What is the difference between cable size and cable rating?

Cable size refers to conductor dimensions, while cable rating includes the allowable electrical and thermal operating conditions.

8. Why does temperature matter?

Conductor resistance generally increases with temperature, affecting voltage drop and power loss.

Conclusion

The Cable & Wire Size Calculator provides practical conductor-area estimates, voltage-drop calculations and AWG/mm² conversions. By clearly displaying its assumptions and engineering limitations, it helps users understand the electrical calculations without confusing preliminary estimates with final cable approval.

Explore companion electronics and circuit calculators for component decoding, DC/AC analysis, filtering, timing, and RF design.